A wet spot under a radiator valve looks alarming and usually is not. If the water is appearing where the valve head meets its body, on the little shaft you turn, the seal around that shaft has failed. That is a leaking radiator valve gland, and it is one of the few heating repairs where the fix costs almost nothing and takes about twenty minutes. It happens most often to valves that have sat untouched all summer and are turned for the first time in October, because the packing inside has dried and compressed.
Make Sure It Really Is the Gland
Dry the whole valve and the piping below it with paper towels, then wrap a strip of dry paper loosely around the body and leave it for half an hour. Where the paper darkens tells you the truth. Water on the stem, under the head, means the packing. Water at the nut where the valve joins the copper pipe means the compression joint and its ferrule. Water at the union where the valve screws into the radiator itself means that connection or the radiator spud. Only the first one is a gland problem, and treating a compression leak as a gland leak wastes an afternoon. Our guide on a leaking radiator valve walks through the other two.
One more clue: a gland leak normally appears or worsens while the valve is being turned and settles to a slow bead afterward. A joint leak drips at the same rate no matter what you do to the head.
Turn the Water Off First
You can do this without draining the system, but you must isolate the radiator at both ends. Close the valve you are working on by turning it fully clockwise, or by winding a thermostatic head down to its off position. Then go to the other end of the radiator, pull the cap off the balancing valve at that end and close it with a small wrench or pliers, counting the exact number of turns as you go, because you have to open it by the same amount afterward or that radiator will never heat properly again.
- Lay old towels under the valve and keep a bowl and a pitcher within reach.
- Close the control valve fully clockwise, and close the balancing valve at the far end, counting the turns.
- Loosen the bleed screw at the top of the radiator a fraction to release pressure, then tighten it back up.
- Have a cloth ready. There will be a little water in the valve body even with both ends closed.
Try a Quarter Turn Before Anything Else
The gland nut is the small hexagonal nut immediately beneath the head or handwheel, sitting around the stem. It is not the large nut lower down that grips the pipe. Pull the head off first: on a manual valve it is usually a small screw in the top, and on a thermostatic head it is a ring you unscrew by hand once the head is turned to its highest setting. With the gland nut exposed, hold the valve body steady with one wrench and turn the gland nut clockwise with another, no more than a quarter of a turn.
Refit the head, open the valve, and watch. Roughly half the time that quarter turn compresses the old packing enough to seal it and you are finished. Resist the urge to keep going. Overtightening does not squeeze harder, it distorts the packing, makes the valve stiff to turn, and on an old brass valve can crack the body or disturb the ferrule on the joint below, turning a five-minute job into a plumbing repair.
Re-pack the Gland with PTFE Tape
If the leak survives that quarter turn, the packing is finished and needs replacing. With the radiator still isolated, undo the gland nut fully and lift it up the stem. Underneath you will find the remains of the original packing, often a gray or black fibrous ring, sometimes a rubber O ring. Pick it out with a small screwdriver or an awl and wipe the recess clean.
- Tear off about 8 inches of PTFE tape and twist it along its length into a thin string.
- Wind that string clockwise into the recess around the stem, three or four turns, packing it down with a small screwdriver as you go.
- Slide the gland nut back down and do it up finger tight, then a further quarter to half turn with a wrench.
- Refit the head, open the control valve, then reopen the balancing valve by the exact number of turns you counted.
- Work the valve fully open and closed twice and watch the stem for a full minute.
Where the original was an O ring rather than fiber, a replacement O ring of the same size is a neater repair than tape, and most plumbing supply stores sell mixed packs for a few dollars. Some people use a smear of silicone grease on the stem to keep the new packing supple, which does no harm. A leaking radiator valve gland that has been re-packed carefully should then stay dry for years, so if yours leaks again within a season, look past the packing at the valve itself.
Finish the Job Properly
Once the leak has stopped, dry everything and check again the next morning, and again after the heat has run a full cycle, because heat expands brass and a seal that holds cold can leak hot. Top the boiler pressure back up if the gauge has dropped, as our guide on boiler pressure too low explains. If the radiator now runs cold at the bottom or refuses to warm at all, the balancing valve has not gone back to its old setting, and a small adjustment either way usually restores the balance.
When to Call a Professional
Call someone if the valve body itself is leaking or green with corrosion, if the stem is bent or will not turn, if the leak returns within days of a fresh re-pack, or if either compression joint starts dripping while you work. A tired valve is cheap to replace and a good heating contractor will swap it, often for a thermostatic one, in under an hour. Also call rather than experiment if your system is sealed and pressurized and you are not sure how to refill and re-pressurize it, or if the pressure keeps falling afterward, which points at a leak somewhere else and is covered in our guide on a boiler losing pressure overnight.
Common questions
Can I fix a leaking radiator valve gland without draining the system?
Yes, in almost every case. Closing the control valve at one end and the balancing valve at the other isolates the radiator, so only the small amount of water sitting in the valve body escapes. Count the balancing valve turns so you can reopen it to the same position.
Why does my radiator valve leak only when I turn it?
The packing around the stem has hardened and no longer grips as the shaft moves. Turning the valve breaks whatever seal the dried packing was still making, which is why leaks so often start on the first cold day after a summer of the heat being off.
How tight should the gland nut be?
Finger tight plus about a quarter turn with a wrench is the target. If it needs more than that to seal, the packing itself is worn out and should be replaced rather than crushed harder, because overtightening stiffens the valve and can damage the brass.